Projet

Général

Profil

TLS00 » Historique » Version 169

Version 168 (Laurent GUERBY, 22/07/2022 15:24) → Version 169/189 (Laurent GUERBY, 27/07/2022 16:23)

{{>toc}}

h1. TLS00

tetaneutral.net dispose d'une salle associative à l'intérieur du datacenter TLS00 : http://www.tls00.fr/

131 C Chemin du Sang de Serp - 31200 TOULOUSE GPS 43.62036, 1.42140 tourner a gauche GPS 43.62105, 1.42252

Photos :
* salle tetaneutral.net http://pano.tetaneutral.net/data/tls00/20140331/
* onduleur dell http://pano.tetaneutral.net/data/tls00/20140401/
* MMR-B-01 :
** http://pano.tetaneutral.net/data/tls00/20140518/
** http://pano.tetaneutral.net/data/tls00/20140611/

dimensions : 400cm largeur x 552cm profondeur x 350cm hauteur : 22.08 m2 de surface et 77.28 m3 de volume



h2. Cables

* MMR-B-01 : (le plus haut) 12FO vers Myrys 1-6 cable vers boitier TLS00 salle edition
** 1 Myrys 1 porte <=> 8H
** 2 Myrys 1 mur <=> 8B
** 3 Myrys 2 porte <=> 4H TODO migrate to 9H
** 4 Myrys 2 mur <=> 9B
** 5 Myrys 3 porte <=> 10H
** 6 Myrys 3 mur <=> 10B
** 7 a 12 : cave de myrys

* MMR-B-01 : 36FO juste en dessous du 144 vers salle asso http://pano.tetaneutral.net/data/tls00/20140518/IMG_20140518_221934.jpg
** 1H Cogent 10G-LR transit
** 1B Cogent 10G-LR transit
** 2H unused
** 2B ATTENTION ne marche pas
** 3H Fullsave FTTH (2.sw.a2.3.tls00:Eth1/45) was Radisson 1G-LX was Cogent vers s2 SFP M000335
** 3B Fullsave FTTH was Radisson 1G-LX
** 4H unused was Myrys 3 vers s7 port 24 TODO migrate to 9H
** 4B unused
** 5H Fullsave cartoucherie 4v
** 5B Fullsave cartoucherie 4v
** 6H Cogent 10G transit deuxieme port
** 6B Cogent 10G transit deuxieme port
** 7H unused
** 7B unused
** 8H Picto 1 was unused was Myrys 1
** 8B Picto 2 was unused Myrys 2
** 9H FranceIX 1 was unused TODO Myrys 3
** 9B FranceIX 2 was unused Myrys 4
** 10H Myrys 5 vers convertisseur de media 20211229
** 10B unused was: Myrys 6 vers s53 port sfp+1
** 11H Fullsave Transit 10G
** 11B Fullsave Transit 10G
** 12H unused was Prosoluce
** 12B unused Prosoluce
** 13H Ughy
** 13B unused was Fullsave wifi
** 14H Fullsave Transit
** 14B unused was Fullsave CELAN 2417
** 15H TouIX vers port 9 MMR B puis port 21 S1-E03
** 15B TouIX vers port 10 MMR B puis port 22 S1-E03
** 16H s56 was S3-B11 13 jolibrain
** 16B unused was S3-B11 14
** 17H unused was S3-B11 15
** 17B unused was S3-B11 16
** 18H unused
** 18B TOUIX FranceIX BiDi (TX1310/RX1550 40km) VLAN 4031 et 4032 (franceix)

Serial s52 branché sur g1
Serial nexus (n3064e) branché sur g23.



h2. Jolibrain

Baie S3-B11
Livraison 20180226
Acces (ticket + carte identité +empreinte veineuse) : beniz,guerby,mherrb,sileht,eZag

Baie Modele: APC Netshelter SX - AR3107
http://www.apc.com/shop/th/en/products/NetShelter-SX-48U-600mm-Wide-x-1070mm-Deep-Enclosure-with-Sides-Black/P-AR3107

Deux PDU : AP8953 (6kVA chacun 21 prises C13 3 prises C19)
http://www.apc.com/shop/et/en/products/Rack-PDU-2G-Switched-ZeroU-32A-230V-21-C13-3-C19/P-AP8953
http://www.apc.com/salestools/MLAN-9F8QVU/MLAN-9F8QVU_R5_EN.pdf

FSE-PDU-00140 PDU droite (depuis le couloir)
FSE-PDU-00141 PDU gauche

Commandé par jolibrain mais pas arrivé un plateau fixe :
http://www.apc.com/shop/th/en/products/Fixed-Shelf-250lbs-114kg-Black/P-AR8122BLK
Fixed Shelf 250lbs/114kg Black

h3. Hosting Rack

Si vous ếtes interessés par un hébergement rackable inscrivez-vous :

# Nom prénom ou personne morale / nb de U / conso Watt / simple ou double alim / prix mensuel acceptable

# Cebador Bertrand 2backup / 2U / ~100 / ? / ~100e

h2. Boitier

Projet de boitier 4U DIY. Objectifs :
* pour jolibrain 4 GPU et bonne ventilation en 4U (eventuellement 8 si 2 cartes meres)
* pour tetaneutral.net boitier machine cluster 6-8 disques en remplacement des tours actuelles (et routeur PCIe 10G et plus)
* pour DCPBay boitiers N disque durs

Fournisseurs potentiels ci-après, reste à trouver des motivés pour faire le design CAD.

Bénévoles :
# Laurent GUERBY (pas de compétence CAD)
# Nicolas GONZALEZ
# nom prénom

h3. Fournisseur

Via Jean de Trebons (qui se propose de demander un devis) :

http://mecalaser.fr

Via gremi :

http://sotip.com/fr/photos-produits.html

h3. CAD Boitier

Chercher des bases en open hardware.

h4. Backblaze

https://www.backblaze.com/blog/open-source-data-storage-server/
Chassis – We’ve provided all the drawings you should need to build (or to have built) your own chassis. We’ve had multiple metal bending shops use these files to make a Storage Pod chassis. You get to pick the color.
2-D Blueprints – ZIP file: 4.6 MB
3-D Solidworks files – ZIP file: 112.0 MB
STEP files – ZIP file: 26.6 MB
Drive Guide design files – ZIP file: 606 KB

https://f001.backblazeb2.com/file/Backblaze_Blog/Storage-Pod-6/Storage+Pod+6.0+Parts+List.pdf

h4. OpenCompute

http://opencompute.org/wiki/Server/SpecsAndDesigns
https://en.wikipedia.org/wiki/Open_Compute_Project

h2. Consommation

<pre>
Date Heure releve moyenne note
20140527 0.0 kWh
20140704 10h21 110.2 kWh
20140710 18h06 131.6 kWh 148.3 Watt
20140717 23h33 156.1 kWh 169.7 Watt
20140808 00h08 232.4 kWh 151.4 Watt h7+n7+s8+nuc1
20140819 14h56 277.1 kWh 160.2 Watt + 2 onduleurs
20140917 16h07 397.1 kWh 172.2 Watt ajout g1/g2/g3/s9/s4810a le 20140916 a 17h
20140918 23h18 412.4 kWh 490.6 Watt ajout microserver mherrb a 23h
20141002 23h29 605.2 kWh 573.5 Watt n7 eteint, ajout NUC Jocelyn
20141009 11h00 ajout n7+stri par sileht
20141023 10h56 911.9 kWh 624.0 Watt
20141023 12h02 912.7 kWh
20141023 12h28 913.0 kWh 49s 10 impulsions 10 Wh = 734.7 Watt
20141023 12h41 913.2 kWh 742.8 Watt 53s 10 impulsions 10 Wh = 679.2 Watt
20141027 11h37 979.1 kWh 694.2 Watt
20141113 19h18 1265.3 kWh
20141114 14h37 1279.0 kWh
20141118 13h25 1518.0 kWh 713.4 Watt ajout deux onduleurs Eaton Ellipe Eco 1200 a charger
20141210 12h38 1728.1 kWh 364.8 Watt ??? 1928.1
20141212 13h42 1765.3 kWh 759.2 Watt ajout g4
20141215 14h39 1827.7 kWh 854.8 Watt
20141218 16h06 1892.7 kWh 884.3 Watt
20141229 11h33 2122.4 kWh 885.2 Watt ajout mpower1
20150122 11h46 2615.0 kWh 855.2 Watt
20150129 17h30 2766.7 kWh 871.9 Watt ajout g5
20150213 13h38 3111.5 kWh 968.5 Watt ajout NAS dlc+fab + Zotac id2ndr
20150223 10h00 3344.7 kWh 986.7 Watt 36s 10 impulsions 10 Wh = 1000 Watt
20150323 16h55 4032.0 kWh 1015.2 Watt
20150413 13h31 4550.4 kWh 1035.7 Watt 34s 10 impulsions
20150420 09h35 4722.8 kWh 1051.2 Watt 30s 10 impulsions rallumage g6
20150512 16h55 5301.2 kWh 1080.1 Watt
20150601 11h41 5823.9 kWh 1101.0 Watt ajout g8
20150612 16h08 6142.2 kWh 1089.1 Watt
20150716 19h32 7099.6 kWh 1135.0 Watt
20150824 17h36 8203.2 kWh 1152.0 Watt
20150827 10h54 8279.6 kWh 1166.4 Watt
20150925 15h55 9090.2 kWh 1156.3 Watt
20150928 15h25 9173.3 kWh 1162.2 Watt ajout g9 et g10
20151023 17h26 9962.0 kWh
20151027 22h35 10103.6 kWh
20151104 19h34 10419.8 kWh 1397.4 Watt ajout g4 avec CG
20151120 18h27 10964.9 kWh 1423.3 Watt ajout g11 et g12
20151123 17h55 11093.0 kWh 1791.6 Watt
20151124 14h13 11129.8 kWh 1840.0 Watt
20151221 15h18 12202.1 kWh
20151228 11h07 12430.2 kWh 1392.5 Watt
20151229 19h34 12476.0 kWh 1409.0 Watt
20160108 16h08 12804.8 kWh 1390.3 Watt
20160222 15h49 14339.7 kWh 1453.5 Watt
20160311 15h01 14966.4 kWh 1539.8 Watt
20160325 14h26 15485.5 kWh 1547.2 Watt
20160413 14h01 16193.3 kWh 1553.9 Watt
20160415 14h52 16269.3 kWh 1551.0 Watt
20160719 16h46 20055.0 kWh 1641.7 Watt arret g4
20160726 18h18 20307.6 kWh 1490.0 Watt g6 deviens moussaka
20160818 18h37 21182.1 kWh 1517.5 Watt
20160908 12h44 21961.8 kWh 1565.2 Watt
20161017 15h06 23440.1 kWh 1575.4 Watt
20161018 13h15 23476.5 kWh 1643.3 Watt
20161027 15h37 23862.8 kWh 1769.2 Watt
20161028 18h14 23913.0 kWh 1883.7 Watt
20161103 15h26 24184.8 kWh 1925.6 Watt
20161108 15h35 24389.0
20161109 14h12 24426.9 KWh 1675.76 Watt
20161110 16h09 24471.8 KWh 1730.25 Watt
20161114 16h37 24644.9 KWh 1794.40 Watt
20161128 13h11 25229.4 KWh 1757.54 Watt
20161201 10h45 25347.5 KWh 1697.65 Watt
20161207 09h18 25591.2 KWh 1709.58 Watt
20161222 10h33 26230.2 KWh 1768.86 Watt
20170110 17h58 27045.5 KWh 1759.32 Watt
20170207 12h27 28174.6 KWh 1694.12 Watt
20170210 19h25 28309.3 KWh 1705.78 Watt
20170217 18h35 28595.7 KWh 1713.26 Watt
20170224 17h53 28898.5 KWh 1809.92 Watt
20170306 14h31 29321.3 KWh 1786.73 Watt
20170307 18h26 29372.4 KWh 1830.45 Watt
20170309 14h54 29454.9 KWh 1855.32 Watt
20170315 13h18 29725.0 KWh 1896.77 Watt
20170330 10h13 30303.8 KWh 1621.67 Watt
20170410 08h46 30611.9 KWh 1173.49 Watt TODO deuxieme voie ?
20170420 09h31 30897.6 KWh 1186.71 Watt TODO idem
20170619 08h52 32563.1 KWh 1157.12 Watt TODO idem
20211214 18h16 34712.7 kWh
20220127 15h42 35591.1 kWh
20220527 14h24 37919.7 kWh
</pre>

<pre>
(/ (* 1000 (- 24184.8 23913.0)) (+ (* 24 5) (- 24 18.25) 15.4))
(* 10 (/ 3600 36.0))1000.0
(* 10 (/ 3600 24.0))1500.0
(* 10 (/ 3600 20.0))1800.0
(* 10 (/ 3600 18.0))2000.0
(* 10 (/ 3600 14.4))2500.0
(* 10 (/ 3600 12.0))3000.0
(* 10 (/ 3600 10.3))3500.0
(* 10 (/ 3600 9.0))4000.0
</pre>

h2. Historique

h3. Tableau

Jeudi 22 mai 2014 a 18h a TLS00, durée prévue 2h : montage du tableau et finition des prises electriques murales

# Mika
# Laurent
# Yannick
# PG
# Ughy
# Thierry
# Bertrand

Les 5x2 prises 220 sont cablées ainsi que les deux tableaux salle associative et TGBT A (merci Ughy :).

Reste a faire :
# percer et fixer les IRL 20mm au mur
# decouper proprement les caches du tableau
# acheter un disjo 16A et un 10A (eclairage) de plus (coupure 10kA a Rexel).
# trouver un presse cable double 25mm pour brancher la cablette (on a les simple 25mm)
# trucs (mika je me souviens plus du nom) pour fixer la terre sur les baies

h3. Cable 5G16

Norme : marron-noir-gris pour les phases respectivement (L1,L2,L3), bleu pour le neutre et vert-jaune pour la terre.
https://fr.wikipedia.org/wiki/Courant_triphas%C3%A9

A faire : dépose du cable 4G16 et pose du cable 5G16 sur 50 mètres, prévoir environ 2 heures a 2 ou 3 personnes dont une personne qui peut grimper sur echelle et structures (pas Laurent Guerby :)

Qui est disponible et quand ?

Présents le samedi :
# Laurent GUERBY (mercredi 14 mai toute la journée, jeudi 15 jusqu'a 19h - apres c'est [[QJELT]] , vendredi 16 toute journée sauf un rdv, samedi, dimanche, lundi)
# Aymeric (samedi & dimanche toute la journée, du 19 au 23 à partir de 16h) - peut monter sur une echelle - me prevenir mini 12h avant si besoin de moi :)
# Elie (samedi & dimanche)
# Xavier (samedi ou dimanche toute la journée - possibilité vendredi si je suis prévenu en avance), no problemo avec échelle et échafaudage
# Clement Bruche (samedi)

Proposés :
# Rémy Carbon, mercredi, jeudi, vendredi, samedi, toute la journée aussi.
# Kevin Gandriau (vendredi à partir de 18h, ou lundi aprèm, mardi aprèm, mercredi aprèm)

Rendez-vous samedi 17 mai a 14h a TLS00, fin prévue 17h.

Pour ceux qui le souhaitent miam 12h au restaurant okinawa aux pont jumeaux 156 Allée de Barcelone (10mn a pied),
# Laurent Guerby
# Xavier

Pose ok 14h45 a 16h15 donc environ 1h30, le 4G16 est reenroulé dans la salle tetaneutral.net

h3. Equipements

* 7 baies pleine hauteur
* 1 demi baie
* prises : 2 1 0 0 0 2 2 plus 3 total 10 bandeau 9 prises rackable = 90 prises
* plateaux : 6 6 5 9 2 6 6 total 40 rackable extractible sans outil
* 1 bandeau 8 prises IEC alim IEC gros (vertical en baie)
* switch SG3424 neuf : "s8" a configurer
* 36FO recup Mixart entre la MMR-B-01 et la salle associative (soudé)
* Commande de 70m de 4G16 pour relier le tableau 3x32A a la salle asso via fullsave a Rexel => erreur
* Commande de 50m de 5G16 => ok
* Commande compteur electronique via fullsave a Rexel => ok
* Commande disjoncteurs 32A HPI a Rexel => ok
* Commande boitier fibre 36 SC a fullsave pour le 36FO => ok / soudé
* ThomasP peux donner des patch Cat5e 2x24 ports si besoin
* misc (TODO)

* TODO dimensions / porte

* largeur d'equipement 1U = 44cm PC, un PC 19 (largeur) x 41 (hauteur) x 49 (longueur) => typiquement 2 PC en position normale sur un plateau.

* Onduleur
** Proposition K805N de fullsave 4200 VA / W
*** http://pano.tetaneutral.net/data/tls00/20140401/
*** ftp://ftp.dell.com/Manuals/all-products/esuprt_ser_stor_net/esuprt_rack_infrastructure/dell-online-rack-ups-3750r_User's%20Guide_en-us.pdf
*** 66kg + (besoin tableau électrique séparé à voir sorti IEC a priori)
** via FSF on a déja 2 Eaton Ellipse ECO 1200 USB 1200 VA 750W
** Don de Paul gros onduleur manageable (salle Photo) Smart-UPS 2200 : 2200 VA 1980 W / supporte SNMP et ethernet, charge actuelle 25%, format tour 50kg
** En neuf 1200VA 169.95 http://www.ldlc.com/fiche/PB00115604.html 179.89 http://www.materiel.net/onduleur/eaton-ellipse-eco-1200-usb-69606.html

* -perfo acces elec + fibre- Fait

* Support cable

pour le chemin de câble, a la plateforme du batiment :
2 chemin faisant le tour de la salle (sur 3 mur), monté 1 sur l'autre a 40cm , 1 pour l'elec, 1 pour le réseaux,
on met des prises plexo en dessous du chemin réseaux

en 150mm de large 3 m de long 12 x 34,90€ HT ref 9539
2 crapaud de suspension pour fixation au mur (descente et remonté du jus jusqu'au tableau) 2 x 2,05€ HT ref 9545
Eclisse en sachet de 25 10,90€ HT + 14,90 € HT + 7,20€ HT) ref 9543 , 9544, 9551
équerre pour fixation au mur 24 x 6,20€ HT ref 64938
double prise elec 6 x 13,90€ HT ref 43167 soit 12 prises
coffret tertiaire pragma 4 rangés 72 modules 149€ HT ref 46191 la porte 37€ HT ref 46192 option serrure.
manque les fixations (vis et chevilles pour parpaing)

* disjoncteurs

3 disjoncteur magneto thermique differentiel32A
http://www.legrand.fr/ecat_france/410858-disj-diff-dx-6000-vis.html

et 6 disj 16A legrand

TODO Alternatives et suggestions ?

h3. Questions

Si vous avez une question sur le projet :

# Quelle date pour l'installation de machine adhérent ?
## probablement d'ici fin avril / début mai
# Est-ce adapté aux tours ou faut-il avoir des machines rackables ?
## Nous avons des plateaux donc nous acceptons des machines de tout format comme actuellement a Myrys
# Autre ?

h3. Dates

- 27 mars 2014 : passage en passif Myrys - MMR - Cogent
- 27 mai 2014 : allumage du switch s8
- 31 mai 2014 : activation du transit cogent 10G sur h7
- 3 juin 2014 : mise en production de h7
- 3 juin 2014 : allumage du R310 n7 (ex neo Balma)
- ~ 20 juin intervention changement de tiroir electrique servitude

Voir [[DCFullsave]]